Input Calibration
5.4.6 Milliamperes
Refer to Figure 5-7 and wire the controller according to the procedure given in Table 5-9.
Table 5-9 Set Up Wiring Procedure for Milliampere Inputs
Step
Connect the copper leads from the calibrator to the input to be calibrated as shown in
1
Figure 5-7.
2
Place current source at zero before switching on.
3
Following calibration, turn off the current source prior to disconnecting it from the
instrument.
Source
Figure 5-7 Wiring Connections for Milliampere Inputs