Onboard Inputs And Outputs - Honeywell CIPer 50 User Manual

Table of Contents

Advertisement

CIPer
MODEL 50 CONTROLLER – USER GUIDE
TM

Onboard Inputs and Outputs

Onboard
Inputs/Outputs
NTC10kΩ (Type II),
NTC20kΩ (Type II),
0...10V, slow BI 0.4 Hz
Short-circuit protected
against 24VAC
UI (Universal
Input)
NTC10kΩ (Type II),
NTC20kΩ (Type II),
0...10V fix pull-up, slow
BI 0.4 Hz Short-circuit
protected against 24VAC
open = 24 VDC, closed
BI (Binary
2.0 mA, totalizer @ 15 Hz
Input)
max. Short-circuit
protected against 24VAC
AO (Analog
0..11 V (max. 1 mA)
Output)
Relay Normally Open
contact 3A, 250VAC,
30VDC
Relay Normally Open
BO (Binary
contact 10A, 250VAC,
Output)
30VDC
Relay Normally Open
contact with one
common
For all technical details on Onboard Inputs/Outputs, please refer to the CIPer Model 50 Product Datasheet –31-
00197 and CIPer Model 50 Installation & Commissioning Instructions – 31-00233.
31-00198-03
Max. cable
Description
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
WEB-EHSERIESNX26D
length
16
EHSERIESNX26ND
8
2
4
4
4
1
3
WEB-
8
2
4
4
4
1
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Web-ehseriesnx26dWeb-ehseriesnx26nd

Table of Contents