Table 4-31 Ramp/Soak Profile Example (Using 12 Segments); Figure 4-7 Ramp/Soak Profile Example - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Monitoring and Operating the Controller
Ramp/soak profile example
Before you perform the actual configuration, it is recommended that you draw a
Ramp/Soak profile in the space provided for each of the "Program Record Sheets" and
fill in the associated information in the associated Tables. An example of a Ramp-Soak
Profile is shown in Figure 4-7 and Table 4-31. Start setpoint is at 200 degrees F.
Setpoint
Time/Hours 0

Table 4-31 Ramp/Soak Profile Example (Using 12 Segments)

Prompt
Function
STRT SEG
Start Seg.
END SEG
End Seg.
RAMP UNIT Engr. Unit for
Ramp
RECYCLES Number of
Recycles
Deviation
SOAK DEV
Value
PROG END Controller
Status
Controller
STATE
State at end
KEYRESET Reset SP
Program
POWER UP Program
Status at
Power up
HOTSTART PV Hot Start
SEG1RAMP Ramp Time
Soak SP
SEG2 SP
SEG2TIME
Soak Time
SEG3RAMP Ramp Time
250
500
SEG 4
400
°
F
SEG 3
SEG 2
300
SEG 1
200
1
2
3
4

Figure 4-7 Ramp/Soak Profile Example

Segment
Value
1
12
TIME
2
0
LAST SP
HOLD
DISABLE
ABORT
DISABLE
1
1 hr.
2
300
2
1 hr:30 min.
3
1 hr.
UDC3500 Universal Digital Controller Product Manual
SEG 8
SEG 7
SEG 5
SEG 6
5
6
7
8
9
10
11
Prompt
SEG4 SP
Soak SP
SEG4TIME
Soak Time
SEG5RAMP Ramp Time
SEG6 SP
Soak SP
Soak Time
SEG6TIME
SEG7RAMP Ramp Time
Soak SP
SEG8 SP
SEG8TIME
Soak Time
SEG9RAMP Ramp Time
SG10 SP
Soak SP
SG10 TIME
Soak Time
SG11RAMP Ramp Time
SG12 SP
Soak SP
SG12TIME
Soak Time
SEG 9
SG 10
SG 11
SG 12
12
13
14 15
16
17
2076
5
Function
Segment
4
4
5
6
6
7
8
8
9
10
10
11
12
12
Value
400
1 hr.
1 hr:30 min.
250
3 hr:0 min.
2 hr:30 min.
500
0 hr:30 min.
0
400
0 hr:30 min.
3 hr:30 min.
200
0 hr:30 min.
3/07