Function Prompt
Lower Display
RSET7MIN
RSET7RPM
PROPBD8
or
GAIN 4
RATE8MIN
RSET8MIN
RSET8RPM
CYC5 SEC
or
CYC5 SX3
CYC6 SEC
or
CYC6 SX3
3/07
Selections or
Range of Setting
Upper Display
0.02 to 50.00
0.1 to 9999 %
or
0.001 to 1000
0.00 to 10.00 minutes
0.02 to 50.00
1 to 120
1 to 120
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
RESET 7 MINUTES or RSET 7 REPEATS PER
MINUTE parameters are the same as previously
described. This prompt appears only when four PID
sets are enabled.
PROPORTIONAL BAND 8 or GAIN 8, RATE 8, and
RESET 8 parameters are the same as previously
described. This prompt appears only when four PID
sets are enabled.
RATE 8 MINUTES parameter is the same as
previously described. This prompt appears only
when four PID sets are enabled.
RESET 8 MINUTES or RSET 8 REPEATS PER
MINUTE parameters are the same as previously
described. This prompt appears only when four PID
sets are enabled.
CYCLE TIME (HEAT) determines the length of one
time proportional output relay cycle. Defined as
"HEAT" cycle time for Heat/Cool applications.
CYC5 SEC—Electromechanical relays
CYC5 SX3—Solid state relays
ATTENTION Cycle times are in either second or
1/3-second increments depending upon the
configuration of RLY TYPE in the Output Algorithm
Set Up group.
CYCLE TIME 2 (COOL) is the same as above
except it applies to Duplex models as the cycle time
in the "COOL" zone of Heat/Cool applications or for
the second set of PID constants.
CYC6 SEC—Electromechanical relays
CYC6 SX3—Solid state relays
ATTENTION Cycle times are in either second or
1/3-second increments depending upon the
configuration of RLY TYPE in the Output Algorithm
Set Up group.
Configuration
57