3.5 Loop 2 Tuning Set Up Group

Introduction
Tuning consists of establishing the appropriate values for the tuning constants you are
using so that your controller responds correctly to changes in process variable and
setpoint. You can start with predetermined values but you will have to watch the system
to see how to modify them. The Accutune feature automatically selects Gain, Rate, and
Reset on demand.
There can be as many as four PID sets available for Loop 2.
Function Prompts
Function Prompt
Lower Display
PROP BD5
or
GAIN 5
RATE5MIN
3/07

Table 3-5 TUNING 2 Group Function Prompts

Selections or
Range of Setting
Upper Display
0.1 to 9999 %
or
0.001 to 1000
0.00 to 10.00 minutes
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
PROPORTIONAL BAND (simplex) is the percent of
the range of the measured variable for which a
proportional controller will produce a 100 % change
in its output.
GAIN is the ratio of output change (%) over the
measured variable change (%) that caused it.
100%
G =
PB%
where PB is the proportional band (in %)
If the PB is 20 %, then the Gain is 5. And, at those
settings, a 3 % change in the error signal (SP-PV)
will result in a 15 % change in the controller's output
due to proportional action. If the Gain is 2, then the
PB is 50 %.
Also defined as "HEAT" Gain on Duplex models for
variations of Heat/Cool applications.
The selection of Proportional Band or Gain is made
in the CONTROL parameter group under prompt
PBorGAIN.
RATE action, in minutes, affects the controller's
output whenever the deviation is changing; and
affects it more when the deviation is changing faster.
Also defined as "HEAT" Rate on Duplex models for
variations of Heat/Cool applications.
Configuration
55