Alarms; Table 10-30 Set-Up Group - Alarms - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

10.7.21

Alarms

Table 10-30 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Alarms.
Parameter
Description
ID
Alarm 1 Setpoint 1
009
Value
Alarm 1 Setpoint 2
010
Value
Alarm 2 Setpoint 1
011
Value
Alarm 2 Setpoint 2
012
Value
Alarm 3 Setpoint 1
117
Value
Alarm 3 Setpoint 2
118
Value
Alarm 4 Setpoint 1
119
Value
Alarm 4 Setpoint 2
115
Value
3/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-30 Set-up Group – Alarms
Register
Data
Address
Type
Hex
Decimal
0009
009
FP
000A
010
FP
000B
011
FP
000C
012
FP
0075
117
FP
0076
118
FP
0077
119
FP
0073
115
FP
UDC3500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm
R/W
Within the range of selected
parameter or PV span for
deviation alarm