Honeywell UDC3500 Product Manual page 21

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

remain in manual mode if the PLC should fail. Switching from the Auto/Manual Station
to the back-up control mode is accomplished using the Digital Input option.
Moisture Protection—The NEMA4X and IP66 rated front face permits use in
applications where it may be subjected to moisture, dust, or hose-down conditions. UL
and CSA approved as Type 4 protection.
Setpoint Ramp/Soak Programming (Optional)—Enables you to program and store ten
Ramp and ten Soak segments (total of twenty segments) for setpoint programming. Run
or Hold of program is keyboard or remote digital switch selectable.
Enhanced Setpoint Programming (Optional) )—Four Setpoint Programs each of ten
Ramp and ten Soak Segments. Each pair can be concatenated so as to form a single
Setpoint Program of twenty Ramps and twenty Soaks.
Setpoint Rate—Lets you define a ramp rate to be applied to any local setpoint change. A
separate upscale or downscale rate is configurable. A single setpoint ramp is also
available as an alternative.
Output Rate Limiter—A maximum output rate may be configured for both the upscale
and the downscale output directions.
CE Mark—Conformity with 73/23/EEC, Low Voltage Directive and 89/336/EEC, the
EMC Directive as a standard feature.
Approval Body Options—CSA certification and UL listing are available as an option.
Four Sets of Tuning Constants—Four sets of PID parameters can be configured for each
loop and automatically or keyboard selected.
Data Security—Five levels of keyboard security protect tuning, configuration, and
calibration data, accessed by a configurable 4-digit code. Nonvolatile EEPROM memory
assures data integrity during loss of power.
Diagnostic/Failsafe Outputs—Continuous diagnostic routines detect failure modes,
trigger a failsafe output value and identify the failure to minimize troubleshooting time.
High Noise Immunity—The controller is designed to provide reliable, error-free
performance in industrial environments that often affect highly noise-sensitive digital
equipment.
Accutune III™ —This standard feature provides a truly plug and play tuning algorithm,
which will, at the touch of a button or through a digital input, accurately identify and tune
any process including those with deadtime and integrating processes. This speeds up and
simplifies start-up plus allows retuning at any setpoint. The algorithm used is an
improved version of the Accutune II
possibilities are now offered when tuning your process: Fast Tune and Slow Tune.
Fast Tune will tune the process in such a way that the temp is reached faster, a
slight overshoot will be allowed.
Slowtune will minimize overshoot, but it will take more time for the process
temperature to reach the target setpoint.
3/07
TM
UDC3500 Universal Digital Controller Product Manual
algorithm found on earlier controllers. Two