Figure 45 - 16 Point High Level Analog Input Wiring - Honeywell HC900 Installation And User Manual

Process controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams
16 point High Level Analog Input Wiring (Figure 45)
Be sure to set the module DIP switches for voltage or current mode. See page 77.
4 channel Analog Output Module Wiring
An example of Analog Output Module wiring is shown in Figure 46. Specifications for this module and for
other modules are given in the Specifications section of this manual.
Isolation
The four outputs are isolated from each other.
Shield Grounding
Shields must be grounded as described under Shield Grounding at the beginning of this section.
Hazardous voltages exist at terminal blocks.
Using switches at field devices disconnect the field wiring form power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.
Revision 19
06/14
Figure 45 – 16 point High Level Analog Input Wiring
HC900 Process Controller Installation and User Guide
89