10.7.15

Input 4

Table 10-24 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Input 4.
Parameter
Description
ID
Input 4 Type
131
ATTENTION
Changing the Input Type will result in the loss of Field Calibration values and will restore the
Factory Calibration values.
Input 4
132
Transmitter
Characterization
Input 4 High
95
Range Value
3/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-24 Set-up Group – Input 4
Register
Address
Hex
Decimal
4083
16515
4084
16516
005F
95
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Disable
1 – 0-20mA
2 = 4-20mA
3 = 0-5V
4 = 1-5V
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
FP
R/W
–999. to 9999.
Engineering Units
Data Range or
407