D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 4.0 Installation
.
4.6.2

Installing and Wiring Detection Devices

Install and wire detection devices and keypads at
their locations throughout the premises. Do not
connect the control panel yet.
Section 8.0
On-Board Points on page 42
contains instructions for wiring the on-board
points to detection devices. Section 11.0 Arming
Devices on page 65 contains instructions for
wiring the keypads.
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions
packaged with the POPIT modules.
4.6.3

Installing Modules and Outputs

1.
Power down the unit by unplugging the
transformer and disconnecting the battery.
Always power down the unit when
installing modules or outputs, or when
making wiring connections to the
control panel.
2.
Install and wire any modules required for the
installation as described in the module's
installation instructions.
Instructions for the D8125 POPEX Module,
D8128D OctoPOPIT Module, D8129
OctoRelay Module, D811 Arm Status Relay
Module, and D928 Dual Phone Line Switcher
appear in this guide.
Refer to Section Off-Board Points on page 46
for D8125 and D8128D instructions. Refer to
Off-Board Outputs on page 60 for D8129 and
D811 instructions. Refer to Section 7.11
D928 Dual Phone Line Switcher on page 39
for D928 instructions.
3. If using the power outputs at Terminals 7 or
8, refer to Section Programmable Power
Outputs on page 35 for instructions.
4.6.4
Connecting the On-board Points and
Keypads
Connect the on-board points and keypad wiring
to the system. Refer to Section 8.0
Points on page 42 and Section 11.0 Arming
Devices on page 65 for instructions.
4.6.5

Powering Up

Reconnect the battery, then plug in the
transformer. The buzzer sounds for two sec when
the control panel is powered up. Leave the reset
pin in the locked position.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
Yellow Charging Status LED Remains Lit: If the
yellow charging status LED remains lit after five
minutes of powering up the control panel, either
the battery is deeply discharged or too many
powered devices were connected to the control
panel. Combined continuous current draw for
Terminals 3, 8, 24, and 32, and the accessory
connector cannot exceed 1.4 A. Refer to Section
6.0 Power Outputs on page 34 for help.
4.7
When a firmware update is available, installation
of the update is performed using either a ROM
Update Key or using RPS. Refer to the GV4 Series
Control Panel ROM Update Key Instructions on the
underside of the control panel faceplate, or refer
to RPS Online Help.
4.8
If the control panel is not already programmed,
review the Control Panels (D9412GV4/D7412GV4
v2.03) Program Entry Guide (P/N: F01U265459).
Ensure that all accessory modules for desired
features are available for installation.
Use RPS to load a custom program into the
control panel as needed.
4.9
A point chart label is included in the literature
pack. Install the point chart label for fire or
combined fire-and-burglary systems that use
verification points.
Use the Control Panels (D9412GV4/D7412GV4
v2.03) Program Record Sheet (P/N: F01U265460)
to gather the necessary information for
completing the point chart. Fill out the label and
install it on the inside of the enclosure door
(refer to Figure 2 on page 20).
On-Board

4.10 Testing the System

After installing and programming the control
panel, test the system completely. Test the
control panel and all devices for proper
operation.

Updating Control Panel Firmware

Programming the Control Panel

Installing the Point Chart Label

The point chart label is required for
fire systems with verifications points.
Avoid smearing the entries on the
chart. Use the peel-off backing to
press the label in place.