Bosch D9412GV4 Installation And System Reference Manual page 152

Hide thumbs Also See for D9412GV4:
Table of Contents

Advertisement

D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 21.0 Current Ratings Charts
.
Table 40: Standby Battery Requirements
Type
Household Burglary
Bank Safe and Vault
Central Station or Local Fire Alarm
Remote Station or Auxiliary Fire
Alarm
Household Fire Warning
Equipment
Table 41: Current Rating Chart for Standby Battery Calculations
Qty
Model Number
Used
D9412GV4/
______
D7412GV4
B208
______
4
B308
______
B420
5
______
B426
______
B440
______
B441
______
B442
______
B443
______
B450
6
______
B520
______
B820
______
B915
______
B920
______
B921C
______
B930
______
B942/B942W
______
D125B
______
D129
______
D132A
______
D185
______
D192G
______
D1255/D1255B
______
D1255RB
______
D1256RB
______
D1257RB
______
D1260/D1260B
______
D8125
______
D8125MUX
______
D8128D
______
D8129
______
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
Required Capacity
+ 4 min of alarm
72 h (UL 365). Auxiliary power
current for all devices, including
keypads, must be limited to 300 mA
or less to meet this requirement.
24 h + 5 min of alarm operation.
60 h + 5 min of alarm operation.
24 h + 4 min of alarm operation.
A
AC Power On
Normal Current (mA)
Each
Qty
Total
Unit
225
x 1
= 225
35
x Qty
= ______
22
x Qty
= ______
90
x Qty
= ______
100
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
30
x Qty
= ______
15
x Qty
= ______
100
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
25
x Qty
= ______
23
x Qty
= ______
10
x Qty
= ______
245
x Qty
= ______
35
x Qty
= ______
104
x Qty
= ______
104
x Qty
= ______
104
x Qty
= ______
104
x Qty
= ______
140
x Qty
= ______
60
x Qty
= ______
140
x Qty
= ______
25
x Qty
= ______
20
x Qty
= ______
Calculations
B
AC Power Off
Minimum Current (mA)
Each Unit
Qty
Total
225
x 1
= 225
35
x Qty
= ______
22
x Qty
= ______
90
x Qty
= ______
100
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
35
x Qty
= ______
30
x Qty
= ______
15
x Qty
= ______
100
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
25
x Qty
= ______
23
x Qty
= ______
10
x Qty
= ______
245
x Qty
= ______
35
x Qty
= ______
106
x Qty
= ______
106
x Qty
= ______
106
x Qty
= ______
106
x Qty
= ______
140
x Qty
= ______
60
x Qty
= ______
140
X Qty
= ______
25
x Qty
= ______
20
x Qty
= ______
C
In Alarm
Maximum Current (mA)
Each
Qty
Total
Unit
300
x 1
= 300
35
x Qty
= ______
22
x Qty
= ______
90
x Qty
= ______
100
x Qty
= ______
150
x Qty
= ______
150
x Qty
= ______
150
x Qty
= ______
150
x Qty
= ______
30
x Qty
= ______
15
x Qty
= ______
110
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
65
x Qty
= ______
168
x Qty
= ______
25
x Qty
= ______
70
x Qty
= ______
300
x Qty
= ______
100
x Qty
= ______
206
x Qty
= ______
225
x Qty
= ______
225
x Qty
= ______
225
x Qty
= ______
250
x Qty
= ______
60
x Qty
= ______
140
x Qty
= ______
50
x Qty
= ______
1
Refer to footnote
= ______