D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | Appendix A: System Wiring Diagrams
.
19
7350
20
7000
21
6666
Use Non-shielded cable only.
Maximum capacitance of 140nF (140,000 pf) per system. Contact the wire manufacturer for the
capacitance ratings of the wire being used.
Example cable types
Use the following table for examples of cable types and electrical parameters.
Table 49:
Example Cable Types
AWG
MFG/PN
Capacitance
pF/ft
22
Belden
18
5541
Belden
15
1242
Belden
20
5502
Belden
19
5522
18
Belden
22
5302
Belden
22
5322
16
Belden
19.9
HC2758
Belden
23.5
5202
12
Belden
32
5002
Fire alarm applications require NEC cable type FPLR, FPLP, or FPL or the equivalent power
limited fire alarm cables (refer to article 760 of the NFPA 70 code).
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
24
5800
25
5600
26
5385
Resistance/
1000 ft
16.3
17.6
16.2
15.7
6.5
6.4
4.0
4.2
1.56
29
4828
30
4700
31
4516
Max Run
NEC Type
7500
CL3p, CL3R, CL3,
CL3X, CL2P, CL2
CL2R, CL2X, CM
7500
7000
7350
6363
6363
7000
5800
4400
34
4100
35
4000
36
3800
Definition
Class 2 and Class
3 remote control,
communications,
signaling and
power limited
cables
166