D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.6
.
Table 36:
UL 864 Programming Requirements (Continued)
Product Feature/Option
For Ground Fault Enable Switch
(Refer to the
D9412GV4/D7412GV4
Operation and Installation
Guide.)
* Set the Path 1 Poll Rate to 65535 for 24 hr.
The following programmable parameters are recommended by Bosch when installing a commercial fire alarm
system. Always check with your local Authority Having Jurisdiction.
SDI 92 is automatically supervised if used for reporting.
Table 37:
UL 864 Programming Recommendations
Prompt
Phone Line Fail Report
Phone Line Restoral Report
Fire Walk Start Report
Fire Walk End Report
Cancel Report
CC# Scope
CC# Enhanced Command
Center
Reset Sensors
Fire Test
L## Reset Sensors
L## Fire Test
U### User Group
P## Ring Until Restored
P## Cross Point
D# Fire Unlock
17.6.2
Required Programming to Meet UL 636
When using a D9412GV4/D7412GV4 control panel for hold-up operation, a hold-up point should have
the following setting applied to it:
P## Type = 0 (Point is constantly armed regardless of the status of the system.)
P## Invisible Point = Yes (Keypads do not display alarm activity from this point.)
When using Modem 4 communication type, the unique point text should be set to ''Hold-
Up'', or equivalent language per the AHJ.
When using ContactID communication type, because the ContactID system doesn't provide
custom text, the hold-up point should be associated as a ''hold-up'' point at the receiving
station. Set Area # Delay Restorals as follows:
Area # Delay Restorals = No (Restoral report is sent when point restores.)
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
Permitted in
Possible Settings
UL 864? (Y/N)
Yes
Closed = Enabled
Open = Disabled
Possible Settings
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Yes / No
Disable/Enable/Passcode Protect
Disable / Enable / Passcode Protect
Disable / Enable
Disable / Enable
0 to 8
Yes / No
Yes / No
Yes / No
Programming Options
Settings Permitted in
UL 864
Closed
Recommendation
Yes
Yes
Yes
Yes
Yes
Do not program No Keypad
Set to Yes, if applicable
Enable
Enable
If Reset Sensor is set to Passcode
Protect, set this to Enable
If Fire Test is set to Passcode
Protect, set this to Enable
Program as 0
May be required for Waterflow,
otherwise No
Set to No for Fire devices.
No