Locking The Reset Pin; Completing The Installation; Charging The Battery; Installing And Wiring Detection Devices - Bosch D9412GV2 Operation And Installation Manual

Hide thumbs Also See for D9412GV2:
Table of Contents

Advertisement

D9412GV2/D7412GV2 | Operation and Installation Guide | 4.0 Installation
4.5.5

Locking the Reset Pin

Locking the reset pin disables the control panel
(Figure 6). When the control panel is disabled, the
system ignores the keypads and points. CALL FOR
SERVICE appears in keypad displays when the pin is
locked down.
On-board relays (Terminals 6 and 7) and off-board
relays deactivate when the control panel is reset.
Terminal 8 has power when the relay is deactivated.
Activation interrupts power at that terminal. The on-
board relay (Terminal 8) remains deactivated when
the reset pin is locked in the disable position.
Releasing the reset pin from the closed position
resets the control panel. The control panel resets all
its timers, counters, indexes, and buffers. Any points
that restore after a reset do not generate Restoral
Reports.
If the reset pin is placed in the disable position when
all areas are armed, there must be an entry in the
Answer Armed program item. Refer to RPS
Parameters in the D9412GV2/D7412GV2 Program
Entry Guide
(P/N: F01U003636).
Locking the pin in the disable position applies power
to the control panel and charges the battery while the
detection devices and keypads are installed.
Figure 6:
Reset Pin
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
32
RED
POWER +
31
YELLOW
DATA BUS A
30
GREEN
DATA BUS B
29
BLACK
COMMON
1 - Reset pin locked (closed).
2 - Reset pin normal (open).
18
4.6
If not already complete, make the earth ground
connection to Terminal 10 and lock the reset pin in
the closed position.
4.6.1
Connect the battery, then the transformer to allow the
control panel to charge the battery while you complete
the installation. Refer to Section 5.0 Power Supply on
page 23 for instructions.
On-board Buzzer Sounds at Power Up and Reset:
The system performs a series of self-diagnostic tests
of hardware, software, and programming at power up
and at reset. The buzzer on the control panel sounds
during the tests. The self-diagnostics tests complete
in approximately 1 to 3 seconds.
If the control panel fails any test, the buzzer continues
sounding and a System Trouble message appears at
the keypads. Refer to Problems Found during Self
Diagnostics in the D9412GV2/D7412GV2/D7212GV2
Installation and Troubleshooting Quick Reference
Guide (P/N: F01U003638) for a description of each
system trouble message.
Touch Terminal 10 First: If the on-board buzzer
sounds briefly when the control panel is touched, any
static charge you carry discharges to the control
panel.
If the control panel receives an electrostatic
discharge, it might generate Watchdog Reset and
Param Fail events.
1
4.6.2
Install and wire detection devices and keypads at their
locations throughout the premises. Do not connect
the control panel yet.
2
Section 8.0 On-Board Points on page 35 contains
instructions for wiring the on-board points to detection
devices. Section 11.0 Arming Devices on page 58
contains instructions for wiring the keypads.
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions packaged
with the POPIT modules.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04

Completing the Installation

Charging the Battery

Avoid electrostatic discharge. Always
touch Terminal 10, the earth ground
connection, before beginning work on the
control panel.

Installing and Wiring Detection Devices

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv2

Table of Contents