D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.0 Approved Applications
.

17.4.6 UL Listed Two-Wire Smoke Detectors Compatible with the D125B

A D125B Powered Loop Interface Module is required to connect smoke detectors to the on-board
points (1-8).
Table 34:
Two-wire smoke detector compatibility table
Manufacturer
Bosch
System Sensor
* D132A does not operate at 24 V; use only on 12 V powered loops.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
CTN
Series
D263
D263
D263TH
D263THC
D263THS
D285
D285
D285TH
F220-P
F220
F220-PTH
F220-PTHC
F220-135
F220-135F
F220-190F
2W-B
i3
2WTA-B
2WT-B
5151
100
Base
Reversing* Maximum number of detectors
N/A
D287, D288,
D340
F220-B6
N/A
B110LP
per loop
12 V
24 V
8
8
8
8
8
8
8
8
10
10
10
10
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
10
10
93