D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.6
.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values.
Table 36:
UL 864 Programming Requirements
Product Feature/Option
Phone 1 through 4
Phone Supervision
Alarm On Fail
Buzz On Fail
Two Phone Lines
Expand Test Report
Fire Reports
R# Fire Supervisory
Missing
Test Reports
AC Fail Report
AC Restoral Report
Battery Missing Report
Low Battery Report
Battery Restoral Report
R# Service Start Report
R# Service End Report
R# Fire Walk St Report
R# Fire Walk End Report
R# Walk Test St Report
R# Walk Test End Report
AC Fail Time
AC Fail Display
AC Tag Along
AC/Battery Buzz
Bat Fail/Restoral Report
Area 1 Area On
A# Delay Restoral
Verify Time
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
Permitted in
Possible Settings
UL 864? (Y/N)
Yes
24 characters
Yes
0 to 240 sec
No
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes/No
Yes
Yes / No
Required
Yes/No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Yes
1:00 to 90:00 min
Yes
10 to 300 sec
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Required to
Yes / No
send system
status reports
Yes
Yes / No
Yes
10 to 60 sec
Programming Options
Settings Permitted in
UL 864
Program a valid phone number
10 to 200 sec
Set to No
Set to Yes
Set to Yes when using PSTN
communications.
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Enter 1:00
10 to 200 sec
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
60 sec
100