Installation accessories
Wall mounting bracket for manifold
Part no. 7465439
With screws and rawl plugs
a
6.7 DHW heating accessories, general
Safety assembly to DIN 1988
Part no. 7180662, 10 bar (1 MPa)
AT: Part no. 7179666, 6 bar (0.6 MPa)
■ DN 20/R 1
■ Max. heat input: 150 kW
6.8 Accessories for DHW heating with integral DHW cylinder
Impressed current anode
Part no. Z004247
■ Maintenance-free
■ Install in place of the magnesium anode supplied
6.9 Accessories for DHW heating with Vitocell 100-V, type CVWA (300 l/390 l/500 l) and
Vitocell 100-W, type CVWA (300 l)
Vitocell 100-V, type CVWA and Vitocell 100-W, type CVWA
Observe the information on the design of DHW cylinders: See from
page 124.
For DHW heating in conjunction with heat pumps up to 17 kW and
solar collectors; also suitable for boilers and district heating systems
VITOCAL
(cont.)
Divicon
a
mm
Components:
■ Shut-off valve
■ Non-return valve and test connector
■ Pressure gauge connector
■ Diaphragm safety valve
Suitable for the following systems:
■ DHW temperature up to 95 °C
■ Heating water flow temperature up to 110 °C
■ Solar flow temperature up to 140 °C
■ Operating pressure on the heating water side up to 10 bar
(1.0 MPa)
R ¾ and R 1
R 1¼
142
167
VIESMANN
69