Terminal Strip For External Heat Pump Components - Viessmann BW 30 .CS Series Installation And Service Instructions Manual

Table of Contents

Advertisement

Electrical connections

Terminal strip for external heat pump components

Note
See position
D
in diagram on page 30.
400 V~/230 V~ components
External connections
Terminals
Function
12X0
Compressor 1 operating message
12X2
Compressor 2 operating message
12K8/11;14
Heat pump central fault message
Circuit protection from load fuse 5FC1 (observe the maximum total current of 16 A)
Terminals
Function
13X0
Circulation pump, evaporator
Primary side
13X5
Circulation pump, condenser
Secondary side
Terminals
Function
21X1
Circulation pump, groundwater
Heat yield
13X2
Pressure switch, primary circuit/frost
stat
Heat yield
(cont.)
Explanation
Floating N/O contact:
Closed: compressor 1 running
Open: compressor 1 not running
Connection values
Max. voltage: 250 V~
Max. switching current: 4 A (ACS1)
Floating N/O contact:
Closed: compressor 2 running
Open: compressor 2 not running
Connection values
Max. voltage: 250 V~
Max. switching current: 4 A (AC1)
Floating N/O contact:
Closed: no fault
Open: heat pump fault
Connection values
Max. voltage: 250 V~
Max. switching current: 4 A (AC1)
Explanation
Connection values
Max. output: 4000 W
Voltage:
400 V~/230 V~
Max. switching current: 9 A (AC3)
Connection values
Max. output: 4000 W
Voltage:
400 V~/230 V~
Max. switching current: 9 A (AC3)
Explanation
Connection values
Max. output: 4000 W
Voltage:
400 V~/230 V~
Max. switching current: 9 A (AC3)
Note
Fit the service switch upstream of the circulation
pump.
Insert jumper if no safety components are instal-
led.
Installation sequence
31