Setting annunciator (with check time)
ANS
This instruction sets the annunciator (F device).
Ladder diagram
(s)
Setting data
■Descriptions, ranges, and data types
Operand
Remarks
(s)
Timer number for evaluation time
(m)
Evaluation time data
(d)
Annunciator device to be set
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB
(s)
(m)
*2
(d)
*1 Only T can be used.
*2 Only F can be used.
Processing details
• This instruction sets (d) when the command input remains ON continuously for the evaluation time [(m)100 ms, (s)] or
more. This instruction resets the current value of (s) evaluation timer and does not set (d) when the command time is less
than the evaluation time [(m)100 ms]. Also, this instruction resets the evaluation timer when the command input turns
OFF.
Command input
ANS
■Related devices
Device
SM8049
SM8048
SD8049
Operation error
There is no operation error.
5 SEQUENCE INSTRUCTIONS
118
5.3 Output Instructions
(m)
(d)
Word
U\G T, ST,
T, ST, C, D,
C, LC
W, SD, SW, R
*1
(s)
(m)
(d)
Name
ON status annunciator smallest number
enabled
Annunciator operation
ON status annunciator smallest number
Structured text
ENO:=ANS(EN,s,m,d);
Range
1 to 32767
Double word Indirect
U\G
Z
LC
LZ
Command input
(d)
Less than the evaluation
Equivalent to or longer
time
than the evaluation time
((m) less than 100 ms)
((m) 100 ms or more)
Remarks
When SM8049 is turned ON, SM8048 and SD8049 are enabled.
When one of the F devices is operating, SM8048 turns ON.
The smallest number of the F devices that are operating is stored.
Data type
Data type (label)
16-bit signed binary
ANY16
16-bit unsigned binary
ANY16_U
Bit
ANY_BOOL
Constant
specification
K, H
E
$
Others