General-purpose input assignment of the 2-phase 2-input counter
X0
X1
X2
CH1
A
B
CH2
A
CH3
CH4
CH5
CH6
CH7
CH8
• The table below shows the related devices.
Function
CH1
Monitor in operation
SM4500
High-speed counter pulse
SD4507,
density
SD4506
Measurement unit time
SD4517,
SD4516
• The table below shows the related device update timing.
Function
Monitor in operation
High-speed counter pulse density
Measurement unit time
Precautions
• The maximum input frequency of turning the inputs ON and OFF is shown below:
FX5U-32M CPU module
Used input number
X0 to X5
X6, X7
FX5U-64M/FX5U-80M CPU module
Used input number
X0 to X7
X10 to X17
• When the SPD instruction is used, the UP/DOWN pulse input, preset input and enable input operate in accordance with the
contents set by the parameters of the high-speed counter.
• When the measurement time is changed while the SPD instruction is executed, the changed time is applied every time the
measurement time ends.
• When the SPD instruction is started, the high-speed counter and pulse density measurement are started simultaneously.
When the SPD instruction is stopped, only the pulse density measurement is stopped and the high-speed counter is not
stopped.
• When the current value of the high-speed counter is overwritten, a preset input is executed, or the high-speed counter is
reset by the DHCMOV instruction while the SPD instruction is executed, the operation continues, but the pulse density
cannot be measured normally.
• When the SPD instruction is used, pulses per unit time which exceeds the ring length of the high-speed counter cannot be
input.
A: A phase pulse input, B: B phase pulse input, P: Preset input (reset), E: Enable input (start)
X3
X4
X5
X6
B
A
B
A
If one of X1, X3, X5, X7, X11, X13, X15, X17 is specified as a device, an error occurs.
CH2
CH3
SM4501
SM4502
SD4537,
SD4567,
SD4536
SD4566
SD4547,
SD4577,
SD4546
SD4576
R/W
Update timing
R
• When the SPD instruction is executed
• When the HIOEN instruction is executed
R
• When the measurement time is finished
R/W
• When the SPD instruction is executed
X7
X10
X11
X12
P
E
P
B
A
B
P
A
CH4
CH5
CH6
SM4503
SM4504
SM4505
SD4597,
SD4627,
SD4657,
SD4596
SD4626
SD4656
SD4607,
SD4637,
SD4667,
SD4606
SD4636
SD4666
Maximum input frequency
200 kHz
10 kHz
Maximum input frequency
200 kHz
10 kHz
X13
X14
X15
X16
X17
E
P
E
P
E
B
P
E
A
B
P
A
CH7
CH8
SM4506
SM4507
SD4687,
SD4717,
SD4686
SD4716
SD4697,
SD4727,
SD4696
SD4726
Clear
• Power-on
• Reset
• Power-on
• Reset
• Power-on
• Reset
7 APPLICATION INSTRUCTION
7.14 Pulse related instruction
E
E
B
7