■TIMER_10_FB_M
• When the execution condition of (s1) turns on, counting the current value starts. The timer starts counting from "(s3) 10
ms". When it counts up to "(s2) 10 ms", (d2) turns on. The current measurement value is output into (d1).
• When the execution condition of (s1) turns off, the current value is reset to (s3) and (d2) turns off.
• A value in the range of 0 to 32767 can be specified for (s2).
• A value in the range of -32768 to 32767 can be specified for (s3). However, when a negative value is specified, the initial
value is set to 0.
Ex.
[Ladder example]
TIMER_10_FB_M
M0
Coll
10
Preset
ValueOut
D10
1
ValueIn
Status
M10
[Timing chart]
ON
M0
OFF
1
Value of D10
M10
OFF
■TIMER_100_FB_M
• When the execution condition of (s1) turns on, counting the current value starts. The timer starts counting from "(s3) 100
ms". When it counts up to "(s2) 100 ms", (d2) turns on. The current measurement value is output into (d1).
• When the execution condition of (s1) turns off, the current value is reset to (s3) and (d2) turns off.
• A value in the range of 0 to 32767 can be specified for (s2).
• A value in the range of -32768 to 32767 can be specified for (s3). However, when a negative value is specified, the initial
value is set to 0.
Ex.
[Ladder example]
TIMER_100_FB_M
M0
Coll
10
Preset
ValueOut
D10
1
ValueIn
Status
M10
[Timing chart]
ON
M0
OFF
1
Value of D10
90 ms
M10
OFF
10
90 ms
10
27 TIMER FUNCTION BLOCKS
27.1 Timer Function Blocks
27
855