Mitsubishi MELSEC iQ-F FX5 series Programming Manual page 550

Melsec iq-f fx5 series
Hide thumbs Also See for MELSEC iQ-F FX5 series:
Table of Contents

Advertisement

• The following table shows example of search result table configuration and data. (n=10)
Searched device
Searched data
(s1)
(s1) value (example)
(s1)
K100
(s1)+1
K111
(s1)+2
K100
(s1)+3
K98
(s1)+4
K123
(s1)+5
K66
(s1)+6
K100
(s1)+7
K95
(s1)+8
K210
(s1)+9
K88
• The following table shows example of search result table.
Device number
(d)
(d)+1
(d)+2
(d)+3
(d)+4
Precautions
• Comparison is executed algebraically. (-10<2)
• When there are two or more maximum or minimum values in the searched data, the last position of the max/min is stored
respectively.
• When these instructions are driven, five devices ((d), (d)+1, (d)+2, (d)+3, and (d)+4) are occupied for storing the search
result (d). Make sure that these devices are not used in other controls for the machine.
Operation error
Error code
Description
(SD0/SD8067)
2820
The device range specified by (s1) or (d) exceeds the corresponding device range.
3405
The value stored in a device specified by (n) is 0.
7 APPLICATION INSTRUCTION
548
7.17 Data operation instruction
Comparison data
Data position
(s2) value (example)
K100
0
1
2
3
4
5
6
7
8
9
Description
3
0
6
5
8
Search result
Maximum
Same (d)
value (d)+4
 (First time)
 (Last)
Search result item
Number of same data
Same data position (first position)
Same data position (last position)
Minimum value position (last position)
Maximum value position (last position)
Minimum
value (d)+3