Check For Fan Motor Connector (Power Supply Line) - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
CHECK 2

Check for Fan Motor Connector (Power Supply Line)

(1) Turn the power supply OFF.
With the relay connector disconnected, measure the
resistance between UVW phases of the connector (3
cores) at the motor side, then make sure that the
resistance between each phase is balanced and not
short-circuited.
Red
White
Black
CHECK 3
Checking the Thermistors
If the cause of the problem is related to the thermistors,
then the thermistors should be checked prior to changing
the PCB.
To check the thermistors, proceed as follows:
Step
Action
1
Disconnect the thermistor from the PCB.
2
Read the temperature and the resistor value.
Check if the measured values correspond with the values in
3
the table on the next pages.
460
Troubleshooting by Remote Controller
U
V
W
Measure the resistance between
each phase.