Daikin R71FUV1 Service Manual page 256

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Troubleshooting
Caution
Connector is
connected to the
outdoor unit
PCB.
YES
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit
PCB.
CHECK 3
YES
CHECK 3
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
NO
Refer to P.460.
Si20-701_B
Connect the
connector and
turn ON again.
Replace the
thermistor.
Replace the
outdoor unit
PCB.
249