Daikin R71FUV1 Service Manual page 121

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
Capacity setting adaptor
The capacity is set in the PCB's memory IC. A capacity
setting adaptor that matches the capacity of the unit is
required in the following case:
In case the indoor unit PCB installed at the factory is for
some reason changed at the installation site, the capacity
will not be contained in the replacement PCB. To set the
correct capacity for the PCB you have to connect a
capacity setting adaptor with the correct capacity setting
to the PCB. The capacity setting for the PCB will become
the capacity setting of the adaptor because the capacity
setting adaptor has priority.
Troubleshooting
Caution
The
indoor unit PCB
was replaced with a
spare PCB.
YES
Was
the capacity
setting adaptor
mounted when
replacing the
PCB?
NO
114
Troubleshooting by Remote Controller
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
YES
Replace the
indoor unit PCB.
Replace the
indoor unit PCB.
Install a capacity
setting adaptor.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fa71fvekR100fuv1Fh100bveFhc71kveFhc100kveFv100lve ... Show all

Table of Contents