Daikin R71FUV1 Service Manual page 233

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
Remote Controller Display
H3
Applicable Model
R(Y)125 • 140LU
Method of Error Detection
The protection device circuit checks for the continuity in
the high pressure switch.
Error Decision Conditions
When the high pressure switch has no continuity during
the compressor stops operating.
Possible Causes
Defective high pressure switch
Disconnection in harness of high pressure switch
Defective connection of high pressure switch
connector
Defective outdoor unit PCB
Disconnection in lead wire