Si20-701_B
Troubleshooting
Caution
Check LED
on outdoor unit PCB.
(Is the voltage
insufficient?)
Is the
power supply
voltage between
200±10% VAC?
Is the wiring correct?
When the compressor is
running, measure the
voltage between + and -
of electrolytic capacitor
(C+, C-).
Is the
measured voltage
220 VDC or
more?
364
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
YES
NO
YES
NO
YES
YES
NO
Troubleshooting by Remote Controller
External factor
Field factors
Correct the
wiring.
Monitor the
voltage
(Instantaneous
voltage drop)
Replace the
outdoor inverter
PCB.