Daikin R71FUV1 Service Manual page 287

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
A
Is
inverter
output voltage
same in all 3
phases?
Check
main circuit parts.
Note:
If an overcurrent results during motor pre-heating, reset
by remote controller may not be possible.
280
YES
(Note) Within ±5%
between phases U and V,
between V and W and
NO
between W and U.
NG
OK
Troubleshooting by Remote Controller
Inspect
compressor.
Correct the
wiring. Defective
main circuit
parts.
Defective
inverter.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fa71fvekR100fuv1Fh100bveFhc71kveFhc100kveFv100lve ... Show all