Troubleshooting by Remote Controller
Troubleshooting
Caution
Do
LEDs on
outdoor unit PCB
indicate DC output
overcurrent?
YES
Is
the unit
inoperable
using remote
controller?
NO
Disconnect compressor
inverter.
A
Note:
∗1. Guideline values
Model
RZ(Y)71~125L
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
(∗1)
YES
Disconnect compressor
inverter.
The
error is displayed
again.
Check
compressor
for short circuit and
ground fault.
Instantaneous overcurrent detection value
NO
YES
OK
NG
65A
Si20-701_B
Inspect indoor
unit PCB and
remote controller.
Inspect
compressor for
short circuit and
ground fault.
Defective
inverter.
Defective inverter
and compressor.
279