Daikin R71FUV1 Service Manual page 384

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
A
Check
of outdoor
unit micro-computer
normal H1P. Is H1P
blinking?
YES
Check
of outdoor unit
error detection LED.
Is the red LED
OFF?
YES
NO (ON or OFF)
Turn OFF the power
supply and turn the power
ON.
Is H1P blinking?
NO
Is H1P ON?
NO (OFF)
Turn OFF the power
supply, disconnect the
No.2 indoor-outdoor
transmission wire, and
turn power supply restart.
Is H1P blinking?
NO
NO (ON)
Si20-701_B
YES
Resets normally.
External factor
(Noise, etc.).
YES
Replace the
indoor unit PCB.
YES
Replace the
indoor unit PCB.
Replace the
indoor unit PCB
or correct power
supply system.
Outdoor product
diagnosis
END