Troubleshooting by Remote Controller
Troubleshooting
Caution
The high
pressure sensor
is connected to X32A
of outdoor unit
PCB.
YES
Measure the voltage (VH)
between the pins # (1)
and (3) of the above
connector (∗1).
YES
Is the
relationship
between high
pressure and VH
normal?
(∗2)
NO
Note:
∗1: Voltage measurement point
Outdoor unit PCB
Micro-computer
A/D input
∗2 Measure DC voltage here.
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
YES
GND
+5V
Connector Red
(4)
(3)
(2)
(1)
Si20-701_B
Connect the high
pressure sensor
and turn ON
again.
Replace the
outdoor unit
PCB.
Replace the high
pressure sensor.
Red
Black
White
257