Table of Contents

Advertisement

Si20-701_B
PJ
3.78
Remote Controller Display
PJ
Applicable Model
R(Y)-LU, RR-M
Method of Error Detection
Check whether set value (i.e., factory setting value)
written in E
capacity setting adaptor (X26A) is the same as that of
outdoor unit capacity.
Error Decision Conditions
When the set value with the E
the outdoor unit capacity or any capacity setting adaptor
other than that suitable for the applicable PCB is
installed. (However, the error decision is made only when
the power supply is turned ON.)
Possible Causes
Improper set value with E
Improper capacity setting adaptor installed
Defective outdoor unit PCB
336
Defective Capacity Setting
2
PROM or set value with the (replaced)
Troubleshooting by Remote Controller
2
PROM differs from that of
2
PROM