Daikin R71FUV1 Service Manual page 469

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
For outdoor air thermistor
For suction pipe thermistor
For heat exchanger thermistor
For intermediate heat exchanger thermistor
For liquid thermistor
For remote controller thermistor
T°C
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
462
Troubleshooting by Remote Controller
kΩ
361.7719
265.4704
196.9198
147.5687
111.6578
85.2610
65.6705
50.9947
39.9149
31.4796
25.0060
20.0000
16.1008
13.0426
T°C
40
10.6281
45
8.7097
50
7.1764
55
5.9407
60
4.9439
65
4.1352
70
3.4757
75
2.9349
80
2.4894
85
2.1205
90
1.8138
95
1.5575
100
1.3425
105
1.1614
3SA48001 (AD87A001J)
kΩ

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fa71fvekR100fuv1Fh100bveFhc71kveFhc100kveFv100lve ... Show all

Table of Contents