Daikin R71FUV1 Service Manual page 456

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Troubleshooting
Caution
Are the
stop valves
opened?
YES
Is the
check operation
carried out?
YES
Is
indoor -
outdoor and
outdoor - outdoor unit
transmission
wiring
normal?
YES
Note:
Wiring check operation may not be successful if
carried out after the outdoor unit has been OFF for
more than 12 hours, or if it is not carried out after
running all connected indoor units in the fan mode for
at least an hour.
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
NO
Is
indoor-
outdoor and
outdoor-outdoor unit
transmission wiring
normal?
NO
YES
NO
Si20-701_B
Open stop valve.
Replace the
indoor unit PCB.
After fixing
incorrect wiring,
press and hold
the RESET
button on the
master outdoor
unit PCB for 5
seconds.
∗ The unit will not
run for up to 12
minutes.
Wiring check
operation may
not have been
carried out
successfully.
449