Control Via Profibus - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

6.8.2

Control via PROFIBUS

"DP1 (PROFIBUS)" diagnostics LED
The PROFIBUS diagnostics LED is located on the front of the Control Unit. Its states are
described in the following table.
Table 6- 26
Description of the LEDs
Color
State
-----
OFF
Green
Continuous light
Green
0.5 Hz flashing
light
Red
0.5 Hz flashing
light
Red
2 Hz flashing light
Setting the PROFIBUS Address
There are two ways to set the PROFIBUS address:
1. Via p0918
2. Via the PROFIBUS address switches on the Control Unit
The address switch is behind the blanking plate. The blanking plate is part of the scope of
supply.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Cyclic communication is not (yet) running.
Note:
PROFIdrive is ready for communication when the control unit is ready for operation
(see RDY LED).
Cyclic communication is taking place.
Cyclic communication has still not been fully established.
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller did not send a Global Control or it sent a
defective Global Control (GC).
PROFIBUS master is sending incorrect parameter assignment/configuration
Cyclic bus communication has been interrupted or could not be established.
– To set the bus address for a PROFIBUS node using STARTER, first set the rotary
code switches to 0
dec
– Then use parameter p0918 to set the address to a value between 1 and 126.
– The address is set manually to values between 1 and 126 using the rotary coding
switches. In this case, p0918 is only used to read the address.
Description
(00
) and 127
(7F
hex
dec
hex
6.8 Communication via PROFIBUS DP
).
Operation
341