Siemens SINAMICS G150 Operating Instructions Manual page 267

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 6- 1
If a command data set, which does not exist, is selected, the current data set remains active.
Figure 6-4
DDS: Drive data set
A drive data set contains various adjustable parameters that are relevant with respect to
open and closed-loop drive control:
● Numbers of the assigned motor and encoder data sets:
● Various control parameters, e.g.:
The parameters that are grouped together in the drive data set are identified in the
SINAMICS parameter list by "Data set DDS" and are assigned an index [0..n].
It is possible to parameterize several drive data sets. You can switch easily between different
drive configurations (control type, motor, encoder) by selecting the corresponding drive data
set.
One drive object can manage up to 32 drive data sets. The number of drive data sets is
configured with p0180.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Command data set: selection and display
Select bit 1
CDS
p0811
0
0
1
0
2
1
3
1
Example: Switching between command data set 0 and 1
– p0186: Assigned motor data set (MDS)
– p0187 to p0189: up to 3 assigned encoder data sets (EDS)
– Fixed speed setpoints (p1001 to p1015)
– Speed limits min./max. (p1080, p1082)
– Characteristic data of ramp-function generator (p1120 ff)
– Characteristic data of controller (p1240 ff)
– ...
6.3 Basic information about the drive system
Select bit 0
p0810
selected (r0836)
0
1
0
1
Display
active (r0050)
0
0
1
1
2
2
3
3
Operation
265