Table 4- 53
Max. connectable cross-section (due to TM31): 1.5 mm²
4.11.15.1

Commissioning

Commissioning
When commissioning via STARTER, parameters are assigned to "external fault 3" and
acknowledged automatically when option L61 or L62 are selected.
When commissioning via AOP30, the parameter entries required have to be set
subsequently.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Installing the thermostatic switch for the external braking resistor in the monitoring circuit
of the cabinet unit by connecting to the TM31 (with option G60)
Terminal
T1
Thermostatic switch connection: connection with terminal X541:1 (P24 V)
T2
Thermostatic switch connection: connection with terminal X541:5 (DI11)
Description of function
Set the "Expert" access level at the operator panel
<Key-operated pushbutton> - <Access level> - Set "Expert"
and confirm.
Connect digital input 4 (DI4) on the Control Unit to the first
input of "External fault 3".
Connect the "Operation" signal to the second input of
"External fault 3".
Connect "Acknowledge fault" to digital output 15 (DO15) on
the Control Unit.
Electrical installation
4.11 Other connections
143