Procedure for establishing online operation via Ethernet
1. Installing the Ethernet interface in the PG/PC according to the manufacturer's
2. Setting the IP address in Windows XP.
3. Setting the online interface in STARTER.
4. Assigning the IP address and the name via STARTER (node initialization).
Setting the IP address in Windows XP
On your desktop, right-click "Network environment" -> Properties -> double-click on the
network card and choose -> Properties -> Internet Protocol (TCP/IP) -> Properties -> Enter
the IP addresses and the subnet mask.
Figure 5-32
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
specifications
The PG/PC is assigned a free IP address (e.g. 169.254.11.1). The factory setting of the
internal Ethernet interface -X127 of the Control Unit is 169.254.11.22.
The Ethernet interface must be initialized so that the STARTER can establish
communication. Selecting online mode in STARTER.