Basic commissioning: Entering the basic parameters
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
5.5 First commissioning with the AOP30
Entering the basic commissioning
parameters:
If a sine-wave filter (option L15) is
connected, it must be activated in p0230
(p0230 = 3) otherwise it could be destroyed.
p0700: Preset command source
5: PROFIdrive
6: TM31 terminals
7: Namur
10: PROFIdrive Namur
p1000: Preset setpoint source
1: PROFIdrive
2: TM31 terminals
3: Motorized potentiometer
4: Fixed setpoint
Once a setpoint source has been selected
(p1000), the main setpoint p1070 is
defaulted accordingly.
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
To change a parameter value, navigate to
the required selection field and activate with
<F5>.
Another window appears in which you can
- enter the required value directly, or
- select the value from a list.
Final confirmation
Confirm the basic parameters to save them.
Once you have selected "Continue" and
activated your entries with <F5>, the basic
parameters you entered are permanently
saved and the calculations required for
closed-loop control are carried out.