Agilent Technologies 66319B User Manual page 91

Mobile communications dc source
Hide thumbs Also See for 66319B:
Table of Contents

Advertisement

:DVM [:DC]?
:ACDC?
:VOLTage [:DC]?
:ACDC?
:HIGH?
:LOW?
:MAX?
:MIN?
OUTPut[1|2]
[:STATe] <bool>
:COMPensation
:MODE <mode>
:DFI
[:STATe] <bool>
:SOURce <source>
:PON
:STATe <state>
:PROTection
:CLEar
:DELay <n>
:RELay:
:MODE <mode>
:RI
:MODE <mode>
SENSe
:CURRent
[:DC] :RANGe [:UPPer] <n>
:DETector <detector>
:FUNCtion <function>
:LEAD
:STATus?
:PROTection
:STATe <state>
:SWEep
:OFFSet
:POINts <n>
:POINts <n>
:TINTerval <n>
:WINDow [:TYPE] <type>
[SOURce:]
CURRent
[:LEVel]
[:IMMediate][:AMPLitude] <n>
:TRIGgered [:AMPLitude] <n>
:PROTection
:STATe <bool>
CURRent2
[:LEVel]
[:IMMediate][:AMPLitude] <n>
:TRIGgered [:AMPLitude] <n>
DIGital
:DATA [:VALue] <n>
:FUNCtion <function>
RESistance
[:LEVel]
[:IMMediate][:AMPLitude] <n>
:TRIGgered [:AMPLitude] <n>
VOLTage
[:LEVel]
[:IMMediate][:AMPLitude] <n>
:TRIGgered [:AMPLitude] <n>
Table 8-1. Subsystem Commands Syntax (continued)
Returns DVM dc voltage measurement
Returns DVM rms voltage measurement
Returns dc voltage
Returns the total rms voltage (ac+dc)
Returns the HIGH level of a voltage pulse
Returns the LOW level of a voltage pulse
Returns maximum voltage
Returns minimum voltage
Enables/disables the dc source output
Sets output compensation
Enables/disables the DFI output
Selects event source (QUES | OPER | ESB | RQS | OFF)
Set power-on state (*RST | RCL0)
Reset latched protection
Delay after programming/before protection
Specifies the output relay mode (DD, HD, DH, or HH).
Sets remote inhibit operating mode (LATC | LIVE | OFF)
Selects the high current measurement range
Selects the current measurement detector (ACDC | DC)
Configures the measurement sensor ("VOLT" | "CURR" | "DVM")
Returns the setting of the open sense detection circuit
Enables/disables open sense lead detection
Defines the pre/post data capture in the measurement
Define the number of data points in the measurement
Sets the digitizer sample spacing
Sets the measurement window function (HANN | RECT)
Sets the output current limit
Sets the triggered output current limit
Enables/disables current limit protection
Sets the output2 current level
Sets the triggered output2 current level
Sets and reads the digital control port
Configures digital control port (RIDF | DIG | TRIG)
Sets the output resistance
Sets the triggered output resistance
Sets the output voltage level
Sets the triggered output voltage level
Language Dictionary - 8
(HREMOTE | LREMOTE | HLOCAL | LLOCAL)
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

66319d66321b66321d

Table of Contents