Siemens SINAUT MD741-1 System Manual page 64

Egprs/gprs-router
Hide thumbs Also See for SINAUT MD741-1:
Table of Contents

Advertisement

5 External interface
Note
Make sure that the selected remote stations will not be disturbed.
Interval for connection check (minutes)
Specifies the interval at which the connection check ping packets are sent by the
SINAUT MD741-1. This is specified in minutes.
Number of permitted unsuccessful attempts
Specifies how many times it is allowed for all ping packets of an interval not to
receive an answer, i.e. for none of four pinged remote stations to answer, before
the specified action is carried out.
Activity on faulty connection
Renew Connection
The SINAUT MD741-1 re-establishes the connection to EGPRS or GPRS if the
ping packets sent were not answered.
Reboot MD741-1
The SINAUT MD741-1 carries out a reboot if the ping packets sent were not
answered.
Factory settings
The factory settings for the SINAUT MD741-1 are as follows:
Enable connection check
Host name
Interval for connection check
Number of permitted unsuccessful attempts 3 (failed attempts)
Activity on faulty connection
64
No (switched off)
-
5 (minutes)
Renew Connection
C79000-G8976-C236-05
SINAUT MD741-1