Warning
!
Suitable cables for temperatures in excess of 70 °C
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an
air ambient in excess of 50 °C, only use cables with admitted maximum operating
temperature of at least 80 °C.
Warning
!
Protection against transient voltage surges
Provisions shall be made to prevent the rated voltage from being exceeded by
transient voltage surges of more than 40 %. This criterion is fulfilled, if supplies are
derived from SELV (Safety Extra-Low Voltage) only.
2.2

Step by step

Set up the SINAUT MD741-1 in the following steps:
Step
1.
First familiarise yourself with the preconditions for operation
of the SINAUT MD741-1.
2.
Read the safety instructions and other instructions at the
beginning of this document very carefully, and be sure to
follow them.
3.
Familiarise yourself with the control elements, connections
and operating state indicators of the SINAUT MD741-1.
4.
Connect a PC with a Web browser (Admin PC) to the local
interface (X2) of the SINAUT MD741-1.
5.
Using the Web user interface of the SINAUT MD741-1, enter
the PIN (Personal Identification Number) of the SIM card.
6.
Disconnect the SINAUT MD741-1 from the power supply.
7.
Insert the SIM card in the device.
8.
Connect the antenna.
9.
Connect the SINAUT MD741-1 to the power supply.
10.
Set the SINAUT MD741-1 up in accordance with your
requirements.
11.
Connect your local application.