Discharge Pressure Check - Daikin FT25CV1A Service Manual

C-series
Hide thumbs Also See for FT25CV1A:
Table of Contents

Advertisement

Check
5.5

Discharge Pressure Check

Check No.8

Discharge pressure check

118
High
YES
Is the stop valve open?
YES
Is the
connection pipe deformed?
YES
Are the heat exchanger and
air filter dirty?
Not dirty
NO
NO
NO
Dirty
Si01-406
Replace compessor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean.
Replace the compressor.
(R3049)
Service Diagnosis