Discharge Pressure Check - Daikin Altherma EKHBH Series Service Manual

Table of Contents

Advertisement

Additional Checks for Troubleshooting
5.7

Discharge Pressure Check

1
Check No.08
3
3
4
5
3–56
Discharge pressure check
NO
High
YES
NO
Is the stop valve
open?
YES
Is the
NO
connection pipe
deformed?
YES
Are the
NO
heat exchanger and
air filter dirty?
YES
ESIE06-03
Replace compessor.
Open the stop valve.
Replace the pipe installed at the
site.
Clean.
Replace the compressor.
Part 3 – Troubleshooting