1. Model Name Indoor Controller L/I : Wireless Controller M/J : Wired Controller Power Supply V1 : Single Phase, 220-240V, 50Hz Series L : L Series M : M Series P : P Series Capacity Index 10 : Based on Btu/hr Refrigerant Blank : R22 : R410A...
Page 4
Outdoor Power Supply V1 : Single Phase, 220-240V, 50Hz Series C : C Series F : F Series Capacity Index 18 : Based on Btu/hr Refrigerant Blank : R22 : R410A Type of Air-Conditioner R : Single Split Condensing Unit...
2. Features Indoor Air Quality Daikin Cooling King M-series has Plasma Generator which it is an Indoor Air Quality (IAQ) solution to effectively kill the bacteria by damaging microbial DNA and surface structures without being harmful to human tissues. Furthermore, balancing the ionization in your home to combat the ill feelings associated with our stressful lifestyles and creates the refreshing environment resembling the nature. Stylish Flat-Panel Ideal blend of style and function. Regular cleaning is easier by just wiping the flat front panel. This ensures the air-conditioner will always look brand new all the time.
4. Application Information Operating Range Ensure the operating temperature is in allowable range. Cooling Caution : The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. INDOOR TEMP. WB (˚C) DB: Dry bulb WB: Wet bulb Controller DGS01...
Page 15
Fan speed selection • Press the button continuously will toggle the fan speed in the following order: Low → Med → High → Auto • Stop pressing when the desired fan speed appears on the display screen. Operation mode • Press the MODE button to select the type of operating mode. •...
DSLM8 MODE TURBO SWING QUIET TIMER TIMER TIMER OVERRIDE SLEEP Operating Guide MODE Button Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to see in which mode the control is set. *AUTO and DRY are available for selected models only. TURBO Fan Speed Press the Turbo key once to activate Turbo fan speed.
Page 17
“ON TIMER” and “OFF TIMER” The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1 Table 1.1: Timer ON and Timer OFF key press and event sequence.
Page 18
OVERRIDE Function Press the OVERRIDE key once will activate the override function for 1 hour. An indicator “OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function. After the override timer is completed, the override function is deactivated and the logo is OFF.
5. Installations Installation Guideline Safety Precautions WARNING • Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. • All field wiring must be installed in accordance with the national wiring regulation. •...
Installation Diagram Indoor unit Caulk pipe Cut thermal insulation pipe 75mm or more from ceiling hole gap to an appropriate length and with putty. wrap it with tape, making sure that no gap is left in the Front panel insulation pipe’s cut line. Wrap the insulation pipe with the 50mm or more from walls finishing tape from bottom to top.
Installation Of The Indoor Unit Air flow The indoor unit must be installed in such a way so as (Indoor) to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it.
Page 22
Recommended Mounting Plate Retention Spots And Dimensions FT10/15LV1L/M & FT10/15MV1I/J FT20/25LV1L/M, FT20/25MV1I/J FTN10/15PV1L/M & FTN10/15MV1I9/J9 FTN20/25PV1L/M & FTN20/25MV1I9/J9 Recommended mounting Recommended mounting plate Use tape measure as shown. plate retention spots retention spots Position the end of a tape measure (5 spots in all) (7 spots in all) Through...
9.50 (3/8") 6.35 ( 1/4") Example: FT10LV1L & R09CV1 with 12m piping length, additional piping length is 4.5m. Thus, Additional charge = 4.5m x [20g/m] = 90 [g] * Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Page 24
Piping Works And Flaring Technique Figure A • Do not use contaminated or damaged copper Cutting copper tube tubing. If any piping, evaporator or condenser had 1/4t been exposed or had been opened for 15 seconds or more, the system must be vacuumed. Generally do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid...
Page 25
Cooling Unit (single phase) FT10/15LV1L FT20/25LV1L Outdoor Unit Indoor Unit Interconnection Cable Terminal Block Terminal Block FT10/15LV1M FT20/25LV1M FT10/15MV1I FT20/25MV1I COMP COMP Indoor FT10/15MV1J FT20/25MV1J FTN10/15PV1L FTN20/25PV1L Model FTN10/15PV1M FTN20/25PV1M FTN10/15MV1I9 FTN20/25MV1I9 Main Switch Power Supply Cable FTN10/15MV1J9 FTN20/25MV1J9 N / L2 Power R09/15CV1 R18/20/25CV1...
Page 26
• All wires must be firmly connected. • Make sure all the wire do not touch the refrigerant piping, compressor or any moving parts. • The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
Vacuuming And Charging Vacuuming is necessary to eliminate all moisture and air from the system. • Open the gas cylinder and low pressure Vacuuming The Piping And The Indoor Unit charging valve. Except for the outdoor unit which is pre-charged •...
FT L/M, FTN P/M Indicator Lights IR Signal Receiver When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will respond as below to confirm acceptance of the signal transmission. IR Receiver ON to OFF 1 Long Beep OFF to ON 2 Short Beep...
Page 29
LED Indicator Lights : Normal Operation And Fault Conditions For CoolingUnit Error Normal Operation / Action Code COOL (GREEN) – – Cool Mode Green Auto mode in Cooling operation – – Green Timer on – – – – – – –...
Page 30
FT311/FTN311 LED Indicator Lights LED Indicator Lights : Normal Operation And Fault Conditions Operation / Fault Indication Action Power Timer Sleep Timer on Sleep mode on Dry mode on Clean the filter and Frost prevention switch to high fan Continuously Room air sensor contact loose / short Call your dealer once every 2 sec.
Page 31
Air Conditioner Unit Operation Dry Mode • When the air humidity is high, the unit can operate in dry mode. Press <MODE> button and choose <DRY>. • If the room temperature is 2°C/3.6°F higher than the set temperature, the air conditioner will operate under cooling mode until it reaches within the 2°C/3.6°F range of difference compared to the set temperature before it converts to dry mode.
Page 32
Special Precautions When Dealing With Refrigerant R410A Unit (1) What is New Refrigerant R410A? R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.
Page 33
(d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapour composition. (e) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal.
7. Servicing and Maintenance Components Maintenance Procedures Period Air Filter 1. Remove any dust adhering to the filter by using a vacuum cleaner At least once (Indoor Unit) or wash in lukewarm water (below 40˚C) with a neutral cleaning every 2 weeks. detergent. More frequently if 2.
Page 40
Pre Start Up Maintenance (After Extended Shutdown) • Inspect thoroughly and clean indoor and outdoor units. • Clean or replace air filters. • Clean condensates drainline. • Clean clogged indoor and outdoor coils. • Check fan imbalance before operation. • Tighten all wiring connections and panels. •...
8. Troubleshooting When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
9 . Dimensional Data Indoor Unit - FTL & FTM Series FTNP & FTNM Series THE MARK SHOWS PIPING DIRECTION REAR REAR LEFT RIGHT TOP VIEW NAME PLATE SIGNAL RECEIVER TERMINAL BLOCK WITH INDOOR UNIT EARTH ON/OFF SWITCH BOTTOM BOTTOM SIDE VIEW TERMINAL ROOM TEMPERATURE LOUVER FRONT GRILLE FIXED SCREWS THERMISTOR (INSIDE)
Page 43
(5 spots in all) Through the wall hole Ø 65mm Drain hose position Liquid pipe end Gas pipe end ALTERNATIVE INSTALLATION PLATE : FT10/15LV1L, FT10/15LV1M & FT10/15MV1L, FT10/15MV1J FTN10/15PV1L, FTN10/15PV1M & FTN10/15MV1I9, FTN10/15MV1J9 All dimensions are in mm Dimension Model FT10/15LV1L FT10/15LV1M FTN10/15PV1L...
Page 44
(7 spots in all) Through the wall hole Ø 65mm Liquid pipe end Gas pipe end Drain hose position INSTALLATION PLATE: FT20/25LV1L, FT20/25LV1M & FT20/25MV1I, FT20/25MV1J FTN20/25PV1L, FTN20/25PV1M & FTN20/25MV1I9, FTN20/25MV1J9 All dimensions are in mm Dimension Model FT20/25LV1L FT20/25LV1M 1065 310 FTN20/25PV1L FTN20/25PV1M...
Page 45
Outdoor Unit Model: R09/15CV1 All dimensions are in mm Dimension Model R09CV1 600 475 245 418 177 398 101 97 700 521 250 485 175 441 130 111 R15CV1...
Page 46
Outdoor Unit Model: RN10/15FV1 All dimensions are in mm Dimension Model RN10/15FV1 550 658 273 16...
Page 47
Outdoor Unit Model: R18/20/25/31CV1 RN20/25/28CV1 All dimensions are in mm Dimension Model R18/20CV1 855 628 328 520 179 46 93 149 101 113 603 126 164 17 RN20/25CV1 R25/31CV1 855 730 328 533 182 44 93 149 101 113 603 126 164 17 RN28CV1 Dimension Model...
10. Exploded View & Part List Indoor Unit Model : FT10/15LV1L, FT10/15LV1M DESCRIPTION DESCRIPTION ASSY., FRONT GRILLE ASSY, INSTALLATION PLATE PANEL RIGHT SIDE PANEL AIR FILTER DRIP PROOF COVER FRONT GRILLE CLIP, COIL SENSOR ASSY, CONTROL BOX ASSY, HEAT EXCHANGER ASSY, SERVICE COVER ASSY, DRAIN HOSE ASSY, PIPING FIXTURE FAN BEARING VIBRATION ABSORBER SET MOTOR...
Page 49
Indoor Unit Model : FTN10/15PV1L, FTN10/15PV1M DESCRIPTION DESCRIPTION ASSY, INSTALLATION PLATE ASSY., FRONT GRILLE PANEL RIGHT SIDE PANEL AIR FILTER DRIP PROOF COVER CLIP, COIL SENSOR FRONT GRILLE ASSY, CONTROL BOX ASSY, HEAT EXCHANGER ASSY, SERVICE COVER ASSY, DRAIN HOSE ASSY, PIPING FIXTURE FAN BEARING VIBRATION ABSORBER SET MOTOR...
Page 50
Indoor Unit Model : FT10/15MV1I, FT10/15MV1J FTN10/15MV1I9, FTN10/15MV1J9 DESCRIPTION DESCRIPTION ASSY, INSTALLATION PLATE ASSY., FRONT GRILLE RIGHT SIDE PANEL PANEL DRIP PROOF COVER AIR FILTER FRONT GRILLE CLIP, COIL SENSOR ASSY, HEAT EXCHANGER ASSY, CONTROL BOX ASSY, SERVICE COVER ASSY, DRAIN HOSE ASSY, PIPING FIXTURE FAN BEARING VIBRATION ABSORBER SET MOTOR...
Page 51
Indoor Unit Model : FT20/25LV1L, FT20/25LV1M DESCRIPTION DESCRIPTION ASSY., CONTROL BOX ASSY., CHASSIS ASSY., PCB (WITH LAMP COVER) MOTOR CONTROL BOX COVER BLOWER, CROSS FLOW FAN BUSH SERVICE COVER MOTOR COVER ASSY., MOUNTING PLATE ASSY., INDOOR COIL ASSY., FRONT COVER ASSY., AIR DISCHARGE HOUSING FRONT COVER ASSY., LOUVER...
Page 52
Indoor Unit Model : FTN20/25PV1L, FTN20/25PV1M DESCRIPTION DESCRIPTION ASSY., CONTROL BOX ASSY., CHASSIS ASSY., PCB (WITH LAMP COVER) MOTOR CONTROL BOX COVER BLOWER, CROSS FLOW FAN BUSH SERVICE COVER MOTOR COVER ASSY., MOUNTING PLATE ASSY., FRONT COVER ASSY., INDOOR COIL FRONT COVER ASSY., AIR DISCHARGE HOUSING ASSY., LOUVER...
Page 53
Indoor Unit Model : FT20/25MV1I, FT20/25MV1J FTN20/25MV1I9, FTN20/25MV1J9 DESCRIPTION DESCRIPTION ASSY., PCB (WITH LAMP COVER) ASSY., CHASSIS CONTROL BOX COVER MOTOR SERVICE COVER BLOWER, CROSS FLOW ASSY., MOUNTING PLATE FAN BUSH ASSY., FRONT COVER MOTOR COVER FRONT COVER ASSY., INDOOR COIL PANEL ASSY., AIR DISCHARGE HOUSING FILTER...
Page 54
Indoor Unit Model: FT311V1L, FT311V1M FTN311V1L, FTN311V1M DESCRIPTION DESCRIPTION LED LIGHT BRACKET ASSY. INSTALLATION BRACKET ASSY. CHASSIS CONTROL BOX COVER ASSY. DRAIN HOSE PIPING CLAMP FAN BUSH BRACKET AIR SWING MOTOR AIR LOUVER CROSS FLOW FAN ASSY. AIR DISCHARGE HOUSING FAN BUSH ASSY., INDOOR COIL COIL SENSOR CLIP...
Page 55
Outdoor Unit Model : R09/15CV1 DESCRIPTION DESCRIPTION ASSY. BASE PAN RIGHT PANEL ASSY. OUTDOOR COIL ASSY. FRONT PANEL VALVE BRACKET ASSY. CONTROL PANEL COMPRESSOR ASSY. VALVE COVER ASSY. PARTITION ASSY. FRONT GRILLE ASSY. CAP TUBE PLASTIC HANDLE BRACKET, FAN MOTOR RUBBER GROMMET FAN MOTOR PARTS NOT IN DIAGRAM...
Page 56
Outdoor Unit Model : RN10/15FV1 DESCRIPTION DESCRIPTION ASSY. OUTDOOR COIL COMPRESSOR TOP PANEL DISCHARGE PIPE FAN MOTOR BRACKET SUCTION PIPE ASSY PARTITION ASSY. CAP TUBE FAN MOTOR VALVE BRACKET FAN BLADE ASSY. VALVE COVER ASSY. FRONT GRILLE ASSY. CONTROL PANEL ASSY FRONT PANEL RIGHT PANEL ASSY BASE PAN...
Page 57
Outdoor Unit Model : R18/20CV1, RN20/25CV1 DESCRIPTION DESCRIPTION ASSY., BASE PAN TERMINAL COVER PANEL ASSY., OUTDOOR COIL ASSY., CONTROL PANEL MOTOR BRACKET TOP PANEL FAN MOTOR ASSY., FRONT GRILLE FAN BLADE PLASTIC HANDLE ASSY., VALVE COVER VALVE BRACKET ASSY., FLARE VALVE ASSY., CAPE TUBE ASSY., FLARE VALVE SUCTION PIPE...
Page 58
Model : R25CV1, RN28CV1 DESCRIPTION DESCRIPTION ASSY. BASE PAN FRONT PANEL, LEFT ASSY. OUTDOOR COIL TOP PANEL MOTOR BRACKET ASSY. CONTROL PANEL FAN MOTOR TERMINAL CONTROL PANEL FAN BLADE ASSY. VALVE COVER VALVE BRACKET ASSY. FRONT GRILLE PARTITION PLASTIC HANDLE, SIDE COMPRESSOR DISCHARGE PIPE BACK PANEL, RIGHT...
Page 59
Model : R31CV1 DESCRIPTION DESCRIPTION ASSY. BASE PAN ASSY., PANEL FRONT LEFT ASSY. OUTDOOR COIL ASSY, FRONT GRILLE MOTOR BRACKET ASSY , PANEL TOP MOTOR PLASTIC, HANDLE FRONT FAN BLADE PLASTIC HANDLE ASSY. VALVE BRACKET PIPE, SUCTION COMPRESSOR PIPE, DISCHARGE PANEL, SERVICE ASSY.
Page 60