Advanced Settings
Advanced Settings-
Compressor anti-
short cycling time
Set up remote
sensor
or thermostat
Room sensor
calibration
Setting 8
Press "Settings" button to advance to Setting 8.
Press the "Up" or "Down" arrow buttons to
adjust number to the access code 12. Press
"Settings" button to continue onto setting 9
through 19.
Setting 9
Press the "Up" or "Down" arrow buttons to
adjust to the desired time in one minute
increments. Maximum is 10 minutes, minimum
is 0 minutes.
Compressor anti-short cycling time is the amount
of allowable time between compressor stop and
restart. Rapid start/stop of compressors can cause
premature failure. Factory default is 5 minutes.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
Setting 10
Press "Settings" button to advance to Setting
10.
Press the "Up" or "Down" arrow buttons to
adjust to the desired setting.
Remote sensor
Remote interface
Local interface – Through-the-wall
unit only (can also be installed as
option for TTW)
Averaging – Jumper position within
sensors must be adjusted. See page 31.
Setting 15
Press "Settings" button to advance to Setting
15.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration setpoint changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55 Deg F
Setting 15 Set to +4
Display reading = 59 Deg F