Using the setting dial like a potentiometer to perform
operation
4.2 Using the setting dial like a potentiometer to
perform operation
POINT
•Set "1" (extended function parameter valid) in Pr. 30 "extended function
display selection".
•Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting
operation selection".
Operation example Changing the frequency from 0Hz to 60Hz during operation
Operation
1.
Mode/monitor check.
Choose monitor/frequency monitor.
The inverter must be in the
PU operation mode.
Pr. 30 must be set to "1".
Pr. 53 must be set to "1".
2.
Press the
RUN
the inverter.
3.
Turn the
clockwise
until "60.0" appears.
The flickering frequency is
the set frequency.
You need not press the
REMARKS
•If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection" setting may
not be "1".
•Independently of whether the inverter is running or at a stop, the frequency can be set by
merely turning the dial.