Mitsubishi Electric FR-S500 Instruction Manual page 69

Transistorized inverter
Hide thumbs Also See for FR-S500:
Table of Contents

Advertisement

Common specifications
Operational
functions
Operating Status
For meter
Protective/warning function
Ambient
temperature
Ambient humidity
Storage
temperature (*6)
Atmosphere
Altitude, vibration
*1. When undervoltage or instantaneous power failure occurs, no alarm output is provided but
the output is shut off. After power restoration, the inverter may be run as it is. Depending on
the running status (e.g. load magnitude), however, overcurrent, regenerative overvoltage or
other protection may be activated at power restoration. (in the external operation mode)
*2. The braking torque indicated is a short-duration average torque (which varies with motor
loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a
continuous regenerative torque. When the motor is decelerated from the frequency higher
than the base frequency, the average deceleration torque will reduce. Since the inverter
does not contain a brake resistor, use an optional brake resistor when regenerative energy
is large. (The brake resistor can not be used with the 0.1K and 0.2K.) A brake unit (BU)
may also be used.
*3. Compatible with only the product having the built-in cooling fan.
*4. Activated only when "1" is set in Pr. 40 "start-time earth (ground) fault detection selection".
*5. Activated only when external thermal relay input (OH) is selected in any of Pr. 60 to Pr. 63
(input terminal function selection).
*6. Temperature applicable for a short period such as transportation.
Maximum and minimum frequency settings, frequency jump
operation, external thermal relay input selection, automatic
restart after instantaneous power failure, forward/reverse
rotation prevention, slip compensation, operation mode
selection, PID control, computer link operation (RS-485).
1 open collector signal can be selected from
among inverter running, up-to-frequency,
frequency detection, overload warning, zero
current detection, output current detection, PID
upper limit, PID lower limit, PID forward/reverse
rotation, operation ready, current average value
monitor signal, maintenance timer alarm, minor
failure and alarm. 1 contact output (1 contact,
230V 0.3AAC, 30V 0.3ADC) signal can be
selected.
1 signal can be selected from between output frequency and
motor current. Pulse train output (1440 pulses/s, 1mA full
scale)
Overcurrent shut-off (during acceleration, deceleration,
constant speed), regenerative overvoltage shut-off (during
acceleration, deceleration, constant speed), overload shut-
off (electronic thermal relay function), heatsink overheat, fan
failure (*3), stall prevention, brake transistor alarm, brake
resistor overheat protection, start-time output side earth
(ground) fault protection (*4), external thermal relay (*5),
disconnected PU, retry count excess, communication error,
CPU error, undervoltage (*1)
-10°C to +50°C (non-freezing)
(-10°C to +40°C (14°F to 104°F) for totally enclosed
structure feature)
90%RH or less (non-condensing)
-20°C to +65°C
Indoors
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Maximum 1000m above seal level, 5.9m/s
(conforms to JIS C 0040)
64
Use
Pr. 64 and
Pr. 65 for
selection
2
or less