Extended function parameter list
Parameter
Indication
Output frequency
43
detection for reverse
operation
Second acceleration/
44
deceleration time
Second deceleration
45
time
46
Second torque boost
Second V/F
47
(base frequency)
Output current
48
detection level
Output current
49
detection signal delay
time
Zero current detection
50
level
Zero current detection
51
period
Operation panel
52
display data selection
Frequency setting
53
operation selection
FM terminal function
54
selection
Name
Set the reference value at which the signal
(FU) is output when the output frequency
rises to or above a certain value. This
function is valid for reverse operation.
0 to 120Hz, - - -
Second function of the acceleration/
deceleration time set in Pr. 7, Pr. 8.
0 to 999s
Second function for the deceleration time
set in Pr. 8
0 to 999s, - - -
Second function for the torque boost set in
Pr. 0.
0 to 15%, - - -
Second function for the base frequency set
in Pr. 3
0 to 120Hz, - - -
Set the level at which the output current
detection signal (Y12) is output.
0 to
When the output current is at or above the
output current detection level (Pr. 48) for
longer than this period (Pr. 49), the output
current detection signal (Y12) is output.
0 to 10s
Set the level at which the zero current
detection signal (Y13) is output.
0 to
When the output current is at or below the
zero current detection level (Pr. 50) for
longer than this period (Pr. 51), the zero
current detection signal (Y13) is output.
0.05 to 1s
You can choose the data displayed on the
operation panel.
0: Output frequency
1: Output current
100: Set frequency during stop/output
frequency during operation
You can use the setting dial like a
potentiometer to perform operation.
0: Setting dial frequency setting mode
1: Setting dial potentiometer mode
You can choose the indicator connected to
the FM terminal.
0: Output frequency monitor
1: Output current monitor
Description
%
200
%
200
34
Factory
Setting
- - -
5s
- - -
- - -
- - -
150%
0s
5%
0.5s
0
0
0