Mitsubishi Electric FR-S500 Instruction Manual page 16

Transistorized inverter
Hide thumbs Also See for FR-S500:
Table of Contents

Advertisement

3.3.2
Arrangement and wiring of control circuit terminals
A
B
C
Loosen the terminal screw and insert the cable into the
terminal.
Screw size: M3 (A, B, C terminals),
M2 (other than the above)
Tightening torque: 0.5N•m to 0.6N•m (A, B, C terminals)
CAUTION
Undertightening can cause cable
disconnection or malfunction. Overtightening
can cause a short circuit or malfunction due
to damage to the screw or unit.
Cable size: 0.3mm
Screwdriver: Small
(Tip thickness: 0.4mm/tip width: 2.5mm)
*Information on bar terminals
Introduced products (as of July, 2002): Phoenix Contact Co.,Ltd.
Terminal Screw Size
M3 (A, B, C terminal)
M2 (Other than the above)
Bar terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
CAUTION
When using the bar terminal (without insulation sleeve), use care so that the
twisted wires do not come out.
3.3.3
Connection to RS-485 connector
(1) When connecting the parameter unit
Use the optional FR-CB2
operation from the operation panel is not accepted. (
(2) RS-485 communication
Using the RS-485 connector, you can perform communication operation from a
personal computer etc. By connecting the RS-485 connector to computers such as
personal computer and FA with a communication cable, you can run/monitor the
inverter and read/write parameter values using a user program. For further details,
refer to the instruction manual (detailed).
· Conforming standard: EIA Standard RS-485
· Transmission format: Multi-drop link
· Communication speed: Maximum 19200 bps
· Overall extension: 500m
CAUTION
Do not plug the connector to a computer LAN board, fax modem socket,
telephone modular connector etc. As they are different in electrical
specifications, the inverter may be damaged.
PC
SE RUN 10
RL
SD
SD STF STR
0.22N•m to 0.25N•m (other than the
above)
2
2
to 0.75mm
flat-blade screwdriver
Bar Terminal Model
(With Insulation Sleeve)
Al 0.5-6WH
Al 0.75-6GY
Al 0.5-6WH
. When the parameter unit (FR-PU04) is used,
2
5
4
RM RH FM
Wire the stripped cable after
twisting it to prevent it
from becoming loose.
In addition, do not solder it. *
Bar Terminal Model
(Without Insulation Sleeve)
A 0.5-6
A 0.75-6
A 0.5-6
STOP
RESET
11
Control circuit
Cable stripping size
ABC terminals
6
Other than
5
the above
Wire Size (mm
0.3 to 0.5
0.5 to 0.75
0.3 to 0.5
is valid)
(mm)
2
)
3